background image
Overview
The desire for green power and rapid
developments in renewable energy sources are
driving the growth of distributed generation.
Many Power Distribution Companies are
now encouraging small power producers to
interconnect to the Utility grid. Independent
power producers are typically customers who
install small scale generating units up to 10
MW in size to offset their load and sell excess
power to the local distribution Utility for grid
support and reliable supply.
As Distributed Generation (DG) becomes more
prevalent, DG interconnection to the Utility
network requires an affordable, reliable,
and high speed solution that can prevent
power from being fed back to the grid during
undesirable situations, such as power line maintenance, electrical
faults, etc. In the event of a fault, the Distributed Generator needs to
disconnect from the grid prior to the reclosing operation of the Utility
Substation breaker.
The following factors determine the need for automatic Distributed
Generation disconnect from the power grid when the substation
breaker trips open:
· SafetyHazard:Apowerlineassumedtobedisconnectedremains
energized. This can be unsafe for the public, line personnel
working on the feeder, etc.
·DistributedGenerationDamage:IfamainUtilitybreakercloses
out of sync, the Distributed Generator can be damaged
· Customerequipmentdamage:Frequencyandvoltageprovidedto
customers can vary significantly and damage apparatus
GE Digital Energy is the industry leader in introducing a revolutionary
and innovative Distributed Generation disconnect solution that is
high speed, cost effective, wireless, long range, reliable and secure.
Transfer Trip Control System
There are three types of Distributed Generation Trip Control (DGT)
devices available for a wireless transfer trip system.
In a point-to-multipoint system, a first control device is required
at the Utility Substation, a second control device between the
substation and the generation site, and a third control device at
each Distributed Generation site. A point-to-multipoint system can
support up to 7 distributed generation sites.
However, in a point-to-point system, one control is installed at the
Utility Substation and a second control at the Distributed Generation
site. A point-to-point system supports one remote generation site.
Each DGT control device location is based on its respective function.
The substation unit is required to transfer trip signals from the Utility
Substation, the downstream control unit is needed to repeat the
Substation trip signal to each DG site, and the DG site control device
is needed to receive the trip signal from the substation and initiate
the disconnect of the local breaker.
DGT-U
A DGT-U is a trip control device implemented
at the Utility Substation for transferring
wireless trip signals to remote DG sites (up to
7 sites) and receiving status notification back
from each DG site after a trip operation has
been completed. The transfer trip timing is
30 milliseconds.
There is an option to locate a second DGT-U
control at a recloser site on the distribution
feeder. In this instance, the recloser sends a
trip command to the remote DGT-D unit(s).
The DGT-D then responds by initiating a trip
and sending status confirmation back to the
DGT-U at the recloser site and the DGT-U at
the Substation.
Figure 1.
Distributed Generator feeds a faulted grid in the absence of a transfer trip solution.
Figure 2.
Wireless network that allows transfer trip from point to multi-point.
78
DGT
www.GEDigitalEnergy.com
www.GEDigitalEnergy.com
CommunicationsRG.indb 78
5/1/2009 12:36:30 PM