34
x710 Series
www.GEDigitalEnergy.com
Protected Master and Repeater Station
Mission critical applications demand that no single point of failure
can stop the communications system. In wireless applications the
master station serves as the central hub to all remote radios. The x790
Master Station with redundancy option increases the availability of a
system with a hot-standby configuration. The standby radio activates
automatically whenever a fault condition is detected by the active
radio.
For repeater locations, the full-duplex capability of the x790 maximizes
the speed of data traffic relays, for a system with better overall
performance.
Power input (10-16 VDC)
Local management serial port
Connectivity to
controllers via
serial (RS-232)
Rugged industrial housing
Antenna connector
Remote & Master Station
The x710 radio operates in the 200, 400 or 900 MHz licensed frequency
bands.
A radio system is built with a master station and remote radios.
Additionally, the use of repeater stations helps to overcome
obstructions and extend coverage.
x710 radios operate on a specific frequency band, and are tuned at
the factory to the ordered operational range. No field adjustments are
necessary for normal operation.
Specifications
GENERAL
Operational modes
Simplex, half-duplex
Modulation
Digital / CPFSK
Range
Up to 50 miles
1710
RF Data Rate &
bandwidth
3200 @ 6.25 kHz
9600 @ 12.5 kHz
19200 @ 25 kHz
Frequency band
130 - 174 MHz
2710
RF Data Rate &
bandwidth
3200 @ 6.25 kHz
9600 @ 12.5 kHz
19200 @ 25 kHz
Frequency band
216-235 MHz
4710
RF Data Rate &
bandwidth
4800 @ 12.5 kHz
9600 @ 12.5 kHz
19200 @ 25 kHz
Frequency band
330-512 MHz
9710
RF Data Rate &
bandwidth
9600 @ 12.5 kHz
19200 @ 25 kHz
Frequency band
800-960 MHz
TRANSMITTER
Frequency Stability
+/- 1.5 ppm
Carrier power
0.1 to 5 Watts
Programmable
Accuracy
Normal +/- 1.5 dB
Duty Cycle
Continuous
Output Impedance
50 Ohms
RECEIVER
Type
Double Conversion
Superheterodyne
Selectivity
>70dB
Bit Error Rate
1x10-6 @ -110 dBm typical
INTERFACES
Serial
RS232, DCE, DB25 Female
Diagnostic
RS232, DCE, RJ11 Female
Antenna
N-Type Female
MANAGEMENT
MDS InSite software
MDS NetView software
MDS Radio Configuration software
ENVIRONMENTAL
Temperature
-30°C to +60°C (-22°F to
+140°F)
Humidity
95% at 40°C (104°F) non-
condensing
ELECTRICAL
Primary power
(10.5 to 16 Vdc) 13.8 Vdc
nominal
Tx Current
2A Typical at 5 Watts
Rx Current
<125 mA
Sleep mode
15 mA nominal
MECHANICAL
Case
Rugged die-cast aluminum
Dimensions
5.08 H x 14.29 W x 18.4 D
cm. (2.0 H x 5.625 W x 7.25
D in.)
Weight
1 kg (2.2 lb.)
AGENCy APPROVALS
CSA Class 1 Div 2 for hazardous locations
FCC Part 90
Industry Canada & ENTELA
ETSI, EMC, CE MARK (ETSI: ETS 300 113, EMC: EN
300 279)
081216 -v03
· Buyx710throughtheonlinestore
· Downloadguideformspecifications
· Downloaduserdocumentation
· Readapplicationnotesandwhitepapers
View Accessories catalog at www.gemds.com
Accessories for the x710
Visit www.GEMDS.com/x710 to:
Front-panel for configuration
Full-Duplex Radio with redundancy option
Key Pad (Up, Down, Left, Right
Enter, Esc)
KFR-L04-C1 (406-430 MHz)
KFR-L04-C2 (430-450 MHz)
KFR-L04-C3 (450-470 MHz)
KFR-L09-D1 (900 MHz)
Fixed Remote Kits