Predix Edge Applications and Services Release Notes 2.3.2
Bug Fixes
This release contains the following bug fixes:
- OPC-UA Adapter Polling
- 1. Resolved an issue where OPC-UA adapter polling would stop processing data in a block once a tag with bad data quality was encountered. This issue exists in Predix Edge releases 2.3 and 2.3.1.
- Cloud Gateway
- Resolved several resource leaks and stability issues within the Cloud Gateway.
Known Issues
This release has the following known issues:
- Raspberry Pi
- Cloud Gateway on Raspberry Pi is known to fail after running for an extended period of time, due to insufficient memory on the Raspberry Pi device.Note: The Raspberry Pi image remains unchanged from the 2.1.0 release.
- Cloud Gateway Performance
- When the cloud connection is re-established and there is a large store buffer, cloud gateway performance will be slow for a couple of minutes.
- Raw Modbus Data
- Raw modbus data passed from an adapter into a raw modbus sink will fail with an error similar to:
- Couldn't parse {"data":{"tagName":{"val":19}},"timestamp":1562096019014}: std::exception