The following tables outline the steps that you must complete to upgrade this module to
These tasks may be completed by multiple people in your organization. We recommend, however, that the tasks be completed in the order in which they are listed.
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |
Step | Task | Notes |
---|---|---|
1 | On the Process Data Integration Server, upgrade the Process Data Integration Service. |
This step is required. |
2 |
On the Process Data Integration Server, modify the Process Data Integration Service configuration file to specify your OPC Server, the GE Digital APM Server, GE Digital APM database, and login credentials. |
This step is required. |
3 |
On the Process Data Integration Server, start or restart the Process Data Integration Service. |
This step is required. When you start the service, tags from the configured process historian are imported automatically into the GE Digital APM database as OPC Tag records. |
4 |
On the GE Digital APM Server, configure the Meridium Notification Service for PDI. |
This step is required. |
5 | On the GE Digital APM Server, restart the Meridium Notification Service. | This step is required. |
6 | In GE Digital APM, link any new OPC Tag records to related asset records. |
This step is required. |