Troubleshooting
The OPC UA DA collector generates log files during initialization, configuration, and general operation. These can be found in the general logging folder C:\Proficy Historian Data\LogFiles
Troubleshooting Tips
In case the collector does not connect to OPC UA DA server or tags are not displayed:
- Ensure that the certificate is added to Trusted list following Adding a Client Certificate to the Trusted List section.
- Ensure that you have provided a valid User name and Password credentials
- Restart the collector whenever there is any change made to the configuration using Historian Administrator or ClientConfig.ini
- Check that secured Connectivity is true and Enable User security is checked to have connection with User Authentication.
- Ensure that the Souce Server supports Security Policy and Security Mode whenever user sees ‘Matching of secure endpoint not available between server and collector’ error message in the Log File.
- Ensure that the
RetryInitialConnect
andAutomaticReconnect
parameters are set to true in the ClientConfig.ini file.