You should familiarize yourself with the available application features
before you design any group or user account. Very often it is possible
to assign an application feature for a specific application function,
such as the iFIX WorkSpace run-time environment, without providing
access to the entire application. The following table lists the available
application features.
Application Feature Descriptions
Application Feature
|
Allows the user to...
|
Alarm Shelving |
Shelve alarms in run mode. If the Alarm Shelving feature is not enabled for a user, the user will not be able to shelve an alarm even if the alarm shelving is enabled on that block. |
Application Validator
- Creation of Baselines
|
Generate baseline files in the Application Validator.
|
Application Validator
- Run-time Access
|
Run the Application Validator
and generate reports.
|
Background Task Exit
|
Stop any background task such as SAC, or Session Monitor.
|
Batch Execution - [Action Name]
|
Perform a specified action in the Batch Execution
product.
|
Change Management
|
Use Change Management version control features in
iFIX.
|
Data Provider Service |
Use the Data Provider Service feature in iFIX. |
Database Block Add-Delete
|
Add a block to, delete a block from, or modify a block
in a database.
NOTE: In FIX32,
this application feature only allows add and delete functionality.
|
Database Manager
|
Configure individual blocks in a database and import,
export, save, print, query, sort, and summarize the contents of a database.
|
Database Reload
|
Reload the database in memory or load a different
database.
|
Database Save
|
Save the database in memory to disk.
|
EDA Feature 1-55
|
Access an Easy Database Access (EDA) application feature.
You can provide access for up to 55 EDA application features.
|
Electronic Signature - Bypass
|
Bypass the Electronic Signature option, and test an
application without the need to repeatedly enter signatures.
NOTE: Selecting
Add All when you are adding application features to a user or group account
will not add this application feature. You must select it explicitly.
|
Electronic Signature - Perform By
|
Perform signed actions.
|
Electronic Signature - Verify By
|
Verify signed actions.
|
Enable Ctrl-Alt-Del
|
Log off, shut down the computer, access the Windows
Task Manager, or change the computer's password by pressing Ctrl+Alt+Del.
The logged-in user needs this if iFIX is running as
a service and they log off the machine.
|
Enable Task Switching
|
Switch between tasks.
|
FIX32 - [Action]
|
Perform a specified action in a FIX Desktop application.
Be aware that FIX Desktop is no longer supported, as of iFIX 5.8.
|
GE OEM Reserved 1-12
|
Access an application feature defined by an OEM (Original
Equipment Manufacturer). You can provide access for up to 12 OEM application
features.
|
Historical Trend Assign
|
Configure the Classic Historical Assign program.
|
Historical Trend Collection
|
Stop the Classic Historian HTC
program.
|
Historical Trend Export
|
Legacy application feature that is not used in iFIX.
|
iFIX - System Shutdown
|
Shut down iFIX.
|
Manual Failover
|
Allows you to manually initiate a connection or SCADA
failover.
|
OPC UA Configuration Tool |
Run the OPC UA Configuration tool on a SCADA Server, or change and save OPC UA configuration information. |
Project Backup-Restore
|
Back up and restore the iFIX files on the local node.
|
Recipe Builder Development Window
|
Create master and control recipes, enable and disable
the audit trail, assign tag groups to recipes, and scale a batch.
|
Recipe Builder Operations Window
|
Modify control recipes and override recipe items within
specific limits.
|
Recipe Download from Recipe Builder
|
Download recipes from the Recipe Builder.
|
Recipe Load
|
Legacy application feature that is not used in iFIX.
|
Recipe Save
|
Legacy application feature that is not used in iFIX.
|
Recipe Save from Recipe Builder
|
Save recipes.
|
Recipe Text Output from Recipe Builder
|
Create recipe reports, master text recipes, and control
text recipes.
|
Recipe Upload from Recipe Builder
|
Upload recipes from the Recipe Builder.
|
Runtime Visual Basic Editor Access
|
Open the Visual Basic Editor from the run-time environment.
|
Security Configuration
|
Configure the security system, create and delete user
and group accounts, and name security areas.
|
Security Synchronizer
|
Run the Security Synchronizer.
|
Startup Profile Manager
|
Run the Startup Profile Manager application.
|
System Configuration
|
Configure node connections, system paths, alarm services,
and the SCADA configuration for a node.
|
System User Login
|
Log in as the system user.
|
System User Logout
|
Log out as the system user.
|
Tag Group Editor
|
Create, edit, and save tag groups.
NOTE: When you
assign the Tag Group Editor application feature to a user, you must also
assign the WorkSpace Configure application feature to that same user.
If both these application features are not assigned, the user is considered
unauthorized for the Tag Group Editor application.
|
Tag Status
|
View tag staus information.
|
VisiconX Writes
|
Allow VisconX to do writes.
|
WorkSpace Configure
|
Switch to the iFIX WorkSpace configuration
environment.
|
WorkSpace Runtime
|
Switch to the iFIX WorkSpace run-time environment.
|
WorkSpace Runtime Exit
|
Quit the iFIX WorkSpace from the run-time