Application Features

You should familiarize yourself with the available application features before you design any group or user account. Very often it is possible to assign an application feature for a specific application function, such as the iFIX WorkSpace run-time environment, without providing access to the entire application. The following table lists the available application features.

Application Feature Descriptions 

Application Feature

Allows the user to...

Alarm Shelving Shelve alarms in run mode. If the Alarm Shelving feature is not enabled for a user, the user will not be able to shelve an alarm even if the alarm shelving is enabled on that block.

Application Validator - Creation of Baselines

Generate baseline files in the Application Validator.

Application Validator - Run-time Access

Run the Application Validator and generate reports.

Background Task Exit

Stop any background task such as SAC, or Session Monitor.

Batch Execution - [Action Name]

Perform a specified action in the Batch Execution product.

Change Management

Use Change Management version control features in iFIX.

Data Provider Service Use the Data Provider Service feature in iFIX.

Database Block Add-Delete

Add a block to, delete a block from, or modify a block in a database.

NOTE: In FIX32, this application feature only allows add and delete functionality.

Database Manager

Configure individual blocks in a database and import, export, save, print, query, sort, and summarize the contents of a database.

Database Reload

Reload the database in memory or load a different database.

Database Save

Save the database in memory to disk.

EDA Feature 1-55

Access an Easy Database Access (EDA) application feature. You can provide access for up to 55 EDA application features.

Electronic Signature - Bypass

Bypass the Electronic Signature option, and test an application without the need to repeatedly enter signatures.

NOTE: Selecting Add All when you are adding application features to a user or group account will not add this application feature. You must select it explicitly.

Electronic Signature - Perform By

Perform signed actions.

Electronic Signature - Verify By

Verify signed actions.

Enable Ctrl-Alt-Del

Log off, shut down the computer, access the Windows Task Manager, or change the computer's password by pressing Ctrl+Alt+Del.

The logged-in user needs this if iFIX is running as a service and they log off the machine.

Enable Task Switching

Switch between tasks.

FIX32 - [Action]

Perform a specified action in a FIX Desktop application. Be aware that FIX Desktop is no longer supported, as of iFIX 5.8.

GE OEM Reserved 1-12

Access an application feature defined by an OEM (Original Equipment Manufacturer). You can provide access for up to 12 OEM application features.

Historical Trend Assign

Configure the Classic Historical Assign program.

Historical Trend Collection

Stop the Classic Historian HTC program.

Historical Trend Export

Legacy application feature that is not used in iFIX.

iFIX - System Shutdown

Shut down iFIX.

Manual Failover

Allows you to manually initiate a connection or SCADA failover.

OPC UA Configuration Tool Run the OPC UA Configuration tool on a SCADA Server, or change and save OPC UA configuration information.

Project Backup-Restore

Back up and restore the iFIX files on the local node.

Recipe Builder Development Window

Create master and control recipes, enable and disable the audit trail, assign tag groups to recipes, and scale a batch.

Recipe Builder Operations Window

Modify control recipes and override recipe items within specific limits.

Recipe Download from Recipe Builder

Download recipes from the Recipe Builder.

Recipe Load

Legacy application feature that is not used in iFIX.

Recipe Save

Legacy application feature that is not used in iFIX.

Recipe Save from Recipe Builder

Save recipes.

Recipe Text Output from Recipe Builder

Create recipe reports, master text recipes, and control text recipes.

Recipe Upload from Recipe Builder

Upload recipes from the Recipe Builder.

Runtime Visual Basic Editor Access

Open the Visual Basic Editor from the run-time environment.

Security Configuration

Configure the security system, create and delete user and group accounts, and name security areas.

Security Synchronizer

Run the Security Synchronizer.

Startup Profile Manager

Run the Startup Profile Manager application.

System Configuration

Configure node connections, system paths, alarm services, and the SCADA configuration for a node.

System User Login

Log in as the system user.

System User Logout

Log out as the system user.

Tag Group Editor

Create, edit, and save tag groups.

NOTE: When you assign the Tag Group Editor application feature to a user, you must also assign the WorkSpace Configure application feature to that same user. If both these application features are not assigned, the user is considered unauthorized for the Tag Group Editor application.

Tag Status

View tag staus information.

VisiconX Writes

Allow VisconX to do writes.

WorkSpace Configure

Switch to the iFIX WorkSpace configuration environment.

WorkSpace Runtime

Switch to the iFIX WorkSpace run-time environment.

WorkSpace Runtime Exit

Quit the iFIX WorkSpace from the run-time environment.

NOTE: Refer to the Batch Execution documentation for more information about the application features specific to Batch Execution.