Error Symbols

The following explains the error symbols that may appear in Web HMI.

Error SymbolTypeDescription
*****.**
ConfigurationMimic fails to receive data because its data source cannot be found.
####
Configuration/CommunicationMimic fails to subscribe to data from this data source. If all data in the mimic shows this symbol, then the connection to the data server probably failed. If only some data items show this, then those data items may have incorrect syntax.
&&&&&.&&
UnknownMimic receives an undefined error.
@@@@@.@@
CommunicationMimic receives a network error.
?????.??
Out of ServiceMimic cannot receive data because the specified I/O point is off scan.
%%%%%.%%
UncertainMimic receives questionable data, such as out-of-range data.
xxxxx.xx
DeviceMimic cannot receive data because an OPC device is unresponsive.