If a network problem occurs during startup, one of the error codes or messages listed in the following table may appear.

Startup Error Messages 

Error Code

Error Message

Description

1613

Duplicate name in local name table.

iFIX did not shut down properly prior to starting back up. Restart the computer and iFIX.

1622

Name in use on remote node.

The node name assigned to the node is currently in use on another node. Rename one of the nodes to correct this conflict.

8501


8502

Underlying network subsystem not ready.

TCPTASK: Failed to initialize network subsystem.

TCP/IP is not installed properly or is missing. Use PING or TCPTASK to verify that the underlying TCP/IP is set up before attempting to run iFIX.

8503

Windows Sockets API version mismatch.

When attempting to initialize the Winsock TCP/IP interface, TCPTASK detected that the Winsock version is less than 1.1.

 