If a network problem exists that prevents sessions from establishing
or causes sessions to be terminated, one of the error codes listed in
the following table may appear
in the NETDIAG program.
Run-time Error Codes
Error Code
|
Error Message
|
Description
|
1605
|
Command timed out.
|
These errors occur when the remote node is down. When
the remote node is brought back up, the Connection Manager re-establishes
the session.
|
1608
|
Invalid Local Session Number.
|
|
1610
|
Session Closed.
|
|
1624
|
Session Ended Abnormally.
|
|
1620
|
Can't find name called.
|
The session cannot be established because either a
remote node is not operating, a cabling problem exists between the nodes,
or the remote node name is not registered on the network. Verify both
nodes are running compatible network software.
|
1914
|
Connection NOT established with node.
|
The Connection Manager has not yet established a connection
with the remote node. Wait for Connection Manager to establish the session.
|
1960
|
FIX dynamic connection in progress.
|
Connection Manager is in the process of establishing
a dynamic connection with the remote node. Wait for Connection Manager
to establish the session.
|
1964
|
FIX has been shut down on remote node.
|
Connection Manager has detected that iFIX has been
shutdown on the remote node. This error code shows up temporarily and
then changes to 1914.
|
8517
|
Node not found in TCP hosts database.
|
The node name that you are trying to connect to be
resolved to an IP address. The name is probably not in the local hosts
file or on the WINS server. Obtain the remote node's IP address and add
it to the HOSTS file.
|
See Also