Create User-Defined Data Types

Procedure

  1. Access Configuration Hub.
  2. In the NAVIGATION section, under the Configuration Hub plugin for Historian, select Tags.
  3. Select , and then select Manage User-Defined Types.
    The Manage User-Defined Types: <system name> window appears.
  4. Select New Type, and enter values as described in the following table.
    Field Description
    TYPE NAME Enter a name for the user-defined data type (UDT).
    DESCRIPTION Enter a description for the UDT.
    ADMINISTER GROUP Specify the Windows Security Group that you want to assign to the UDT.
    DATA QUALITY Select one of the following options:
    • Store Individual Quality: Select this option to store field-level quality. Storing individual qualities consumes more disk space.
    • Store Master Field Quality: Select this option if you want to assign the same quality as the master field to all the other fields in the UDT. If you select this option, the data sample will have a single quality similar to how an array tag works.
    MASTER Select the radio button corresponding to the field that you want to set as master. When you do so, the data type of this field is used for all the remaining fields in the UDT as well. Only one field can be the master in a UDT. The MASTER column appears only if you select Store Master Field Quality under DATA QUALITY.
    NAME Enter a name for the field.
    DESCRIPTION (under FIELD) Enter a description for the field.
    DATA TYPE Select the data type for the field. If you select Store Master Field under DATA QUALITY, and if you set this field as master, the data type of this field will be applied to the remaining fields in the UDT as well.
  5. For each field that you want to create, select Add Field, and provide the required details.
  6. Select Save Type.
  7. If needed, add more UDTs, and then select Done.
    The UDT is created.

What to do next

Assign the UDT to a tag.