You can reconnect to the OPC Classic HDA
server automatically as soon as the server is up and running. By default, the collector
polls for the server connection every 5 seconds. You can change this interval as well.
The collector is stopped until reconnected to the server.
Procedure
Access the following registry key: HKEY_LOCAL_MACHINE\SOFTWARE\GE
Digital\iHistorian\Services\OPCHDACollector.
Locate the Key created with the ProgID of the OPC Classic HDA
server.
Create a DWORD named EnableOPCHDAReconnect.
Enter the decimal value 1.
If you want to change the reconnection interval (from the default value of 5
seconds):
Create a DWORD named ReconnectInterval.
Enter a decimal value between 5 and 60. This value represents the
number of seconds for the collector to wait before trying to reconnect
to the OPC server.