Collector Status (Failover Triggers) |
If enabled, the collector will fail over if the status changes
to Unknown. |
Watchdog Tag |
Specifies a tag to use to determine the status of the collector.
If the watchdog tag meets any of the conditions specified below, the
secondary collector will be brought on line to replace it. |
Failover on Bad Quality |
If enabled, the secondary collector is promoted when a data
sample from the watchdog tag is received with bad quality. Failover
happens on every write of a bad data sample to the watchdog, not
just on the transition from good to bad quality. |
Failover When Value Transitions from Zero |
If selected, the secondary collector is promoted when a data
sample from the watchdog tag with a non-zero value is received from
the primary collector. Failure happens every time when a non-zero
value is received, not just when the value promotes from zero to
non-zero value. |
Failover When No Value Changes for X Seconds |
If selected, the secondary collector is promoted when no data
value changes have been received within the time period specified.
This could be tied into a heartbeat status indicator. The value is
checked every 5 seconds. To prevent failure, there must be a value
change. |