Sharing Alarms with Other iFIX and FIX Nodes

iFIX 4.0 can share alarms and data with previous versions of iFIX, as well as with FIX32 6.15 and FIX v7.0. FIX32 view nodes will only receive alarms from alarm areas A-P.

NOTE: You cannot run iFIX and FIX 6.x or greater at the same time on a single computer.

iFIX 4.0 will map alarm priorities from legacy systems to the middle three alarm priorities: HIGH, MEDIUM, and LOW.

Outgoing alarms from iFIX 4.0 to iFIX 3.5 or older systems will map CRITICAL, HIHI, and HIGH alarm priorities to a HIGH priority; MEDIUM to a MEDIUM priority; LOW, LOLO and INFO to a LOW priority.