iFIX allows you to display a total count of all disabled alarms on a
particular SCADA server. This includes standard (A-P) and custom (non
A-P) areas.
The following table describes the ASCII and numeric node alarm counters
for disabled alarms.
Node Alarm Counters for Disabled
Alarms
To display a count of
...
|
Use these alarm counters...
|
INFO priority disabled alarms.
|
ALARMCOUNTERS.A_DSABINFO or
ALARMCOUNTERS.F_DSABINFO
|
HIHI priority disabled alarms.
|
ALARMCOUNTERS.A_DSABHIHI or
ALARMCOUNTERS.F_DSABHIHI
|
HIGH priority disabled alarms.
|
ALARMCOUNTERS.A_DSABHI or
ALARMCOUNTERS.F_DSABHI
|
MEDIUM priority disabled alarms.
|
ALARMCOUNTERS.A_DSABMED or
ALARMCOUNTERS.F_DSABMED
|
LOW priority disabled alarms.
|
ALARMCOUNTERS.A_DSABLO or
ALARMCOUNTERS.F_DSABLO
|
LOLO priority disabled alarms.
|
ALARMCOUNTERS.A_DSABLOLO or
ALARMCOUNTERS.F_DSABLOLO
|
INFO priority disabled alarms.
|
ALARMCOUNTERS.A_DSABINFO or
ALARMCOUNTERS.F_DSABINFO
|
Total disabled alarms.
|
ALARMCOUNTERS.A_DSABTOT or
ALARMCOUNTERS.F_DSABTOT
|
Example
To display a count of the total disabled alarms on a SCADA server, enter
the following syntax in a Data link:
FIX32.NODE.ALARMCOUNTERS.F_AREA_DSABTOT