Configuring for Run-time

You can enable specific operator and run-time properties in the Alarm Summary object. The operator properties enable operators to work interactively with the object by acknowledging, deleting, filtering, and sorting alarms at run-time. The run-time properties control time intervals used by the object. The following two tables summarize the operator and run-time properties you can configure.

Alarm Summary Operator Properties 

The property...

Lets operators...

Allow Alarm Acknowledgement

Acknowledge alarms with the Alarm Summary object.

Allow Alarm Deletion

Delete alarms from the Alarm Summary object. Unlike the manual deletion option configured in the SCU, the deleted alarms do not need to be acknowledged first.

Allow Run Time Configuration

Change the filter and sort properties of the Alarm Summary object at run-time.

Enable Column Quick Sort

Sort alarms by clicking a column heading.

Display Right Mouse Menu

Right-click the mouse to display a list of commands to acknowledge, filter, sort, delete, and pause alarms.

Alarm refresh rate

The Alarm Summary object examines the Alarm Summary queue for new alarms.

Data refresh rate

The Alarm Summary object updates the alarm values currently displayed.

Blink rate

An alarm flashes when you enable blinking for it.

Selection Timeout

A row in the spreadsheet remains selected. Typically, the spreadsheet automatically scrolls while receiving new alarms. When you select an alarm from the spreadsheet, the scrolling pauses until the selection timeout expires.

NOTE: You can also acknowledge, delete, filter, and sort alarms in the Alarm Summary object using an Expert or a script. For more information on completing these tasks using an Expert, refer to the Creating Pictures manual. To learn about the iFIX automation interface, refer to the Writing Scripts manual.

See Also