iFIX allows you to display a count of disabled alarms by area on a particular
SCADA server. The following table describes the ASCII and numeric disabled
area alarm counters.
Area Alarm Counters for Disabled
Alarms
To display a count of
all disabled...
|
Use these alarm counters...
|
Alarms in area "area."
|
area.A_AREA_DSABTOT
or
area.F_AREA_DSABTOT
|
CRITICAL priority alarms in area "area."
|
area.A_AREA_DSABCRIT
or
area.F_AREA_DSABCRIT
|
HIHI priority alarms in area "area."
|
area.A_AREA_DSABHIHI
or
area.F_AREA_DSABHIHI
|
HIGH priority alarms in area "area."
|
area.A_AREA_DSABHI
or
area.F_AREA_DSABHI
|
MEDIUM priority alarms in area "area."
|
area.A_AREA_DSABMED
or
area.F_AREA_DSABMED
|
LOW priority alarms in area "area."
|
area.A_AREA_DSABLO
or
area.F_AREA_DSABLO
|
LOLO priority alarms in area "area."
|
area.A_AREA_DSABLOLO
or
area.F_AREA_DSABLOLO
|
INFO priority alarms in area "area."
|
area.A_AREA_DSABINFO
or
area.F_AREA_DSABINFO
|
Example
To display a count of all disabled alarms for area "Line1,"
enter the following syntax in a Data link:
FIX32.NODE.Line1.F_AREA_DSABTOT