Area Alarm Counters for Disabled Alarms

iFIX allows you to display a count of disabled alarms by area on a particular SCADA server. The following table describes the ASCII and numeric disabled area alarm counters.

Area Alarm Counters for Disabled Alarms

To display a count of all disabled...

Use these alarm counters...

Alarms in area "area."

area.A_AREA_DSABTOT or

area.F_AREA_DSABTOT

CRITICAL priority alarms in area "area."

area.A_AREA_DSABCRIT or

area.F_AREA_DSABCRIT

HIHI priority alarms in area "area."

area.A_AREA_DSABHIHI or

area.F_AREA_DSABHIHI

HIGH priority alarms in area "area."

area.A_AREA_DSABHI or

area.F_AREA_DSABHI

MEDIUM priority alarms in area "area."

area.A_AREA_DSABMED or

area.F_AREA_DSABMED

LOW priority alarms in area "area."

area.A_AREA_DSABLO or

area.F_AREA_DSABLO

LOLO priority alarms in area "area."

area.A_AREA_DSABLOLO or

area.F_AREA_DSABLOLO

INFO priority alarms in area "area."

area.A_AREA_DSABINFO or

area.F_AREA_DSABINFO

Example

To display a count of all disabled alarms for area "Line1," enter the following syntax in a Data link:

FIX32.NODE.Line1.F_AREA_DSABTOT